Fixed temperature alarm level The detectors are conventional fixed temperature heat detectors, i.e. they will give an alarm within a response temperature range in accordance with EN54-5:2000.
Cách chơi game đánh bài online-cách hack game bài online
An LED on the detector (not on 6298) will light up when the detector goes into alarm. The detector also has an output for an external LED 2216 / 2217.
The following types are available (static response temperature, class & EN54-5 temp. range):
6295, 57°C, class A2 S (54 to 70°C).
6296, 72°C, class B S (69 to 85°C).
6297, 87°C, class C S (84 to 100°C).
6298, 117°C, class E S (114 to 130°C).
The detectors are latching, i.e. they will not be automatically reset if the temperature, after the alarm, falls below the detector’s static response temperature. The detector’s LED and a connected ext. LED will be lit until the detector is reset via the c.i.e.
The detectors 6295 and 6296 complies with the ATEX classification Ex II 3GD EEx nA II T5. See also the opposite side of this page.
Waterproof connection box The heat pick-up shield, the LED, all electronics, etc. are mounted in a grey water- proof detector housing, to be mounted on the attached connection box, which has three cable inlets. Three compression glands and a silicon gasket for IP67 are also attached.
A label holder intened for a label showing “zone number”, can be mounted in the connection box.
The detectors 6295-6298 are provided with three pairs of flying leads with female push- on connectors, see figure on the opposite side of this page. (Zone line cables (in / out) and an external LED.)
The detectors can be used in the systems EBL500 / 512 / 128 / 1000 / 2000 provided with some zone line inputs for the system respectively (e.g. an 8 zones expansion board 1580 / 4580 input, an addressable zone interface 2226 / 2335 input, an addressable multi purpose I/O unit 3361 input, etc.).
Heat detectors are normally used in rooms where the temperature can be expected to rise rapidly in case of a fire or places where smoke detectors can not be used.
The detectors are intended for outdoor use or indoor use in high humidity premises.
Technical data |
|
Voltage (V DC) rated
allowed normal |
24
12-30 24 (zone line voltage) |
Current consumption at nom. voltage, quiescent (mA) | 0 |
Current limitation required, when active (mA)
(EBL equipment has current limitation.) |
6295-6297: Must be min. 6 and max. 40
6298: Must be min. 6 and max. 30 |
Ext. LED output voltage (V)
max. current output (mA) |
Zone line voltage minus 2 V
10 (no internal current limiter) |
Alarm resistance (Ω) | For 6295-6297: approx. 400. For 6298: approx. 680 |
Ambient temperature (°C) operating
(Min. / Typical / Max.) storage |
6295 (A2 S): 6296 (B S): 6297 (C S): 6298 (E S):
-40 /+25 /+50 -40 /+40 /+65 -40 /+55 /+80 -40 /+85/+110 -45 to +70 -45 to +70 -45 to +70 -45 to +70 |
Ingress Protection rating | IP67 (attached conn. box, silicon gasket and compression glands required) |
Static response temperature | 57, 72, 87, or 117°C depending on detector / class. See text. |
Size Æ x h (mm) | Detector: 95 x 42 Connection box: 100 x 35
Detector + Connection box: 100 x 75 (excl. compression glands) |